Control unit – TREND NX Variable Speed Drives User Manual

Page 77

Advertising
background image

60 • vacon

CABLING AND CONNECTIONS

Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205

6

6.2 Control

unit

The control unit of the frequency converter consists roughly of the control board and additional boards (see
Figure 6-21 and Figure 6-22) connected to the five

slot connectors

(A to E) of the control board. The control

board is connected to the power unit through a D-connector (1) or fibre optic cables (FR9).

Figure 6-21. NX control board

Figure 6-22. Basic and option board connections

on the control board

Usually, when the frequency converter is delivered from the factory, the control unit includes at least the
standard compilation of two basic boards (I/O board and relay board) which are normally installed in slots
A and B. On the next pages you will find the arrangement of the

control I/O and the relay terminals

of the

two basic boards, the

general wiring diagram

and the

control signal descriptions

. The I/O boards mounted

at the factory are indicated in the type code. For more information on the option boards, see Vacon NX
option board manual (ud741).

The control board can be powered externally (+24V, ±10%) by connecting the external power source to
either of the bidirectional terminala #6 or #12, see page 63. This voltage is sufficient for parameter setting
and for keeping the fieldbus active.

Note! If the 24V inputs of several frequency converters are parallelly connected we recommend to use a
diode in terminal #6 (or #12) in order to avoid the current to flow in opposite direction. This might damage
the control board. See picture below.

A

B

C

D

E

+

-

#6

#7

+

-

#6

#7

+

-

#6

#7

+

-

#6

#7

nk6_17

External

+24V