Oven Installation

For Australia, if installing with a flexible hose assembly, the assembly must be certified to
AS/NZS 1869, and be Class B or D.

For Standard Ovens, if installing with a flexible gas hose, the installation must comply with
either ANSI Z21.69 or CAN/CGA-6.16 and a disconnect device complying with either ANSI
Z21.41 or CAN-6.9.

The installation must conform with local building codes, or in the absence of local codes, with
the National Fuel Gas Code, ANSI Z223.1, latest version, Natural Gas Installation Code, CAN/
CGA-B149.1, or the Propane Installation Code, CAN/CGA-B149.2, as applicable.

Gas Supply Requirements for Australian, Standard. & World Ovens

Gas Type

Min kPa

Max kPa

Min “WC

Max “WC

Natural

1.5

3.5

6.0

14

LP

2.75

3.5

11.5

14

The gas supply shall have a gas meter and regulator large enough to handle all of the gas

appliances, such as the furnace, water heater, and ovens in operation at the same time. Add up all
of the Btu/kw/MJ ratings to determine the total load. The installation must conform to local build-
ing codes.

1. The appliance and its individual shutoff valve must be disconnected from the gas supply pip-

ing system during any pressure testing of that system at test pressures in excess of 3.5 kPa or
½-psi.

2. The appliance must be isolated from the gas supply piping system by closing its individual

manual shutoff valve during any pressure testing of the gas supply piping system at test pres-
sures equal to or less than 3.45 kPa or ½-psi.

Minimum and maximum inlet pressures are as follows:

All installations must conform to local building and mechanical codes.