8-8

„When the AC type

Power Cord Specifications

Connecting the Power Cord

When connecting the AC type power cord, be sure to follow the procedures given below.

(1)

Be sure that the GP’s power cord is not plugged in to the power supply.

(2)

Remove the Terminal Srtip’s clear plastic cover.

(3)

Remove the screws from the two (2) terminals (L, N) and FG (Frame Ground) Terminal, position the

Ring Terminals and reattach the screws. (Check each wire to make sure the connections are correct.)

(4)

Reattach the Terminal Strip’s clear plastic cover.

• Use copper conductors only.

AC Power Cord

Grounding Wire

Power Cord

Double-insulated Wire
1.25 to 2.0mm

2

(16-14AWG)

1.25 to 2.0mm

2

(16-14AWG)

Recommended
Ring Terminal

*1

*1

In order to prevent a short circuit caused by loose screws, make sure to

use a crimp-type terminal with insulating sleeve.

J.S.T. Mfg. Co., Ltd
V2-MS3 compatible

J.S.T. Mfg. Co., Ltd
V2-P4 compatible

• The torque required to tighten these screws are as follows:

Terminal Block: 0.5 to 0.6N

•m[5-7Lb•In.]

FG (Frame Ground) Terminal: 0.6 to 0.7N

•m

l

ess than

6.0mm

Φ3.2mm or more

l

ess than

7.0mm

Φ4.3mm or more

FG (Frame Ground) Terminal