GP3000 Series Hardware Manual

8-10

Wiring

When connecting the Power Cord, use the following items when performing wiring. (Items are made by

Phoenix Contact.)

Connecting the Power Cord

When the GP-3200/3300/3400 series is used;

(1)

Confirm that the power cord is unplugged from the power supply.

(2)

When using GP-3200/3300 Series, remove the power connector (plug) from the main unit.

(When using GP-3400 Series, the power connector (plug) is packaged with other accessories.)

(3)

Strip the membrane of the power cord, twist the wire ends, and connect them to the Power Connector.

(4)

Reattach the Power Connector (plug).

Recommended Driver

SZF 1-0.6x3.5 (1204517)

Recommended Pin
Terminals

AI 0.75-8GY (3200519)
AI 1-8RD (3200030)
AI 1.5-8BK (3200043)
AI 2.5-8BU (3200522)

Recommended Pin
Terminal Crimp Tool

CRIMPFOX ZA3 (1201882)

• Be sure to remove the connector from the GP unit prior to starting wiring. Failure to

do so may cause an electric shock.

• The temperature rating of field installed Conductors:75

o

C only.

• Use a flat-blade screwdriver (Size 0.6 X 3.5) to tighten the terminal screws.

The torque required to tighten these screws is 0.5 to 0.6N

•m[5-7Lb•In.].

• Do not solder the cable connection. Doing so may damage the unit due to abnormal

heat or cause a fire.

Be sure to twist the power cords together, up to the power connector.

Power
Connector
(Socket)

Right side

Power Connector (Plug)

(AGP-3300T)