GP3000 Series Hardware Manual

8-16

„Emergency Stop Circuit

Do not process emergency stop signals with a software program by inputting the signal to the GP.

Configure the emergency stop circuit externally to the GP as shown in the figure below:

„Interlock Circuit 1

To use the GP or a PLC to control a motor circuit for forward/reverse rotation, configure the interlock circuit

shown below externally to the GP.

Emergency stop button
b (normally closed) contact

100 to 240VAC

or

24VDC

GP

Machine to be
controlled

Input

Output

GP

Motor forward rotation
signal

Motor reverse rotation
signal

Auxiliary b (normally closed)
contact of electromagnetic switch
for motor reverse rotation

Auxiliary b contact of
electromagnetic switch for
motor forward rotation

Electromagnetic
switch for motor
forward rotation

Electromagnetic
switch for motor
reverse rotation