Loop Name
Assign a two-character name to the loop. This name is shown
on the single loop display in place of the loop number.
Selectable values: 0 to 9, A to Z, %, /,
°
(degree symbol).
Input Units
For loops with temperature sensor input types, choose a
temperature scale: Fahrenheit or Celsius. For a linear or
pulse loop, choose a three-character description of the
loop’s engineering units.
Selectable values: The table below shows the character
set for input units.
Table 4.7
Input Character Sets
Input Reading Offset
If the input type is a thermocouple or RTD, specify the off-
set to correct for signal inaccuracy at a given point. For ex-
ample, at temperatures below 400˚ F, a type J
thermocouple may be inaccurate or “offset” by several de-
grees. Use an independent thermocouple or your own cali-
bration equipment to find the offset for your equipment.
A positive value increases the reading and a negative value
decreases it.
Selectable values: See Table 4.8.