Cls204 and cls208 voltage inputs – Watlow CLS200 User Manual
Page 198

Chapter 9: Troubleshooting and Reconfiguring
CLS200 Series User’s Guide
182
Watlow Anafaze
Doc.# 0600-3050-2000
CLS204 and CLS208 Voltage Inputs
For each voltage input on a CLS204 and CLS208 controller
you must install two resistors. The resistances must be cor-
rect for the expected input range. Note the resistor pack
(RP) locations have three through holes. Install the RD re-
sistor as indicated in the illustration below.
Table 9.8
Resistor Values for CLS204 and
CLS208 Voltage Inputs
Resistor tolerance:
±
0.1%
Table 9.9
Resistor Locations for CLS204 and
CLS208 Voltage Inputs
Resistor Values
Input Range
RC
RD
0 to100mV
Î
(dc)
499
Ω
750
Ω
0 to 500mV
Î
(dc)
5.49 k
Ω
750
Ω
0 to 1V
Î
(dc)
6.91 k
Ω
442.0
Ω
0 to 5V
Î
(dc)
39.2 k
Ω
475.0
Ω
0 to 10V
Î
(dc)
49.9 k
Ω
301.0
Ω
0 to 12V
Î
(dc)
84.5 k
Ω
422.0
Ω
Resistor Locations
Loop
RC
RD
1
R58
RP1
2
R56
RP2
3
R54
RP3
4
R52
RP4
5
R50
RP5
6
R48
RP6
7
R46
RP7
8
R44
RP8
RP#
RD