CLS204 and CLS208 RTDs and Thermistors
For each RTD or thermistor input on a CLS204 or CLS208
controller, you must install three resistors: RA, RB, and
RC. The resistance must be correct for the expected input
range. RA and RB are a matched pair of resistors. Install
them in the resistor pack (RP) locations as shown in the il-
lustration below.
Table 9.10 Resistor Values for CLS204/208
RTD and Thermistor Inputs
Resistor tolerances: RA/RB matched to 0.02% (2 ppm/˚C)
and absolute tolerance is 0.1% (10 ppm/˚C) RC accurate to
0.05%.
Table 9.11 Resistor Locations for CLS204/208
RTD and Thermistor Inputs
Resistor Values
Input
RA/RB
RC
RTD1
10.0 k
Ω
80
Ω
RTD2
25.0 k
Ω
100
Ω
Resistor Locations
Loop
RA/RB
RC
1
RP1
R57
2
RP2
R55
3
RP3
R53
4
RP4
R51
5
RP5
R49
6
RP6
R47
7
RP7
R45
8
RP8
R43
RP#
RA RB