Chapter 6: Enhanced Features
CLS200 Series User’s Guide
116
Watlow Anafaze
Doc.# 0600-3050-2000
Figure 6.3 Application Using Process Vari-
able Retransmit
To set up this application, you would do the following:
1.
First, set up the standard control loop parameters ac-
cording to the furnace application, in this case on loop
1.
2.
Select another unused PID output for retransmitting
the thermocouple value (for example, loop 2 heat out-
put).
3.
Change the display to loop 2, and then enter the three-
key sequence (
ENTER, then ALARM ACK, then CHNG SP)
and go to the first screen in Table 6.1.
4.
Follow the steps in Table 6.1 to configure the process
variable retransmit option.
5.
After following the steps in Table 6.1, press
BACK sev-
eral times until the normal loop display appears. The
controller will now produce an output on loop 2 which
is linear and proportional to the loop 1 process vari-
able.
CLS200
Furnace
Power
Controller
To Data
Logger
Loop 1 PID Output
Loop 2 PID Output
Heater
Loop 1
Input
Process
Variable
Serial
DAC