CLS200 Series User’s Guide

Chapter 4: Setup

Doc.# 0600-3050-2000

Watlow Anafaze

83

Input Type

Specify the type of input sensor used on this loop:

•

Thermocouple type J, K, T, S, R, B or E.

•

RTD 1 or RTD 2.

•

Linear input.

•

Skip (an input type available for unused loops).
Alarms are not detected, and the scanning display
does not show loops that are set to SKIP.

•

Pulse input (available only for loop 5 on CLS204, loop
9 on CLS208 or loop 17 on CLS216).

Selectable values: See Table 4.6.

Table 4.6

CLS200 Input Types and Ranges

Input

Type

Input Range

J T/C

-350 to +1,400

°

F (-212 to +760

°

C)

K T/C

-450 to +2,500

°

F (-268 to +1,371

°

C)

T T/C

-450 to +750

°

F (-268 to +399

°

C)

S T/C

0 to +3,200

°

F (-18 to +1,760

°

C)

R T/C

0 to +3,210

°

F (-18 to +1,766

°

C)

B T/C

+150 to 3,200

°

F (+66 to 1,760

°

C)

E T/C

+150 to 3,200

°

F (+66 to 1,760

°

C)

RTD1

-148.0 to +572.0

°

F (-100.0 to +275.0

°

C)

RTD2

-184 to +1,544

°

F (-120 to +840

°

C)

PULSE

0 to 2 kHz

SKIP

Loop not used.

LINEAR

See

Linear Scaling Parameters on page 86.

ALARM

01 INPUT
TYPE ? J T/C