Input Type
Specify the type of input sensor used on this loop:
•
Thermocouple type J, K, T, S, R, B or E.
•
RTD 1 or RTD 2.
•
Linear input.
•
Skip (an input type available for unused loops).
Alarms are not detected, and the scanning display
does not show loops that are set to SKIP.
•
Pulse input (available only for loop 5 on CLS204, loop
9 on CLS208 or loop 17 on CLS216).
Selectable values: See Table 4.6.
Table 4.6
CLS200 Input Types and Ranges
Input
Type
Input Range
J T/C
-350 to +1,400
°
F (-212 to +760
°
C)
K T/C
-450 to +2,500
°
F (-268 to +1,371
°
C)
T T/C
-450 to +750
°
F (-268 to +399
°
C)
S T/C
0 to +3,200
°
F (-18 to +1,760
°
C)
R T/C
0 to +3,210
°
F (-18 to +1,766
°
C)
B T/C
+150 to 3,200
°
F (+66 to 1,760
°
C)
E T/C
+150 to 3,200
°
F (+66 to 1,760
°
C)
RTD1
-148.0 to +572.0
°
F (-100.0 to +275.0
°
C)
RTD2
-184 to +1,544
°
F (-120 to +840
°
C)
PULSE
0 to 2 kHz
SKIP
Loop not used.
LINEAR
Linear Scaling Parameters on page 86.
ALARM
01 INPUT
TYPE ? J T/C