Serial dac inputs – Watlow CLS200 User Manual
Page 226

Chapter 11: Specifications
CLS200 Series User’s Guide
210
Watlow Anafaze
Doc.# 0600-3050-2000
Table 11.35 Serial DAC Agency Approvals /
Compliance
Serial DAC Inputs
The Serial DAC requires a proprietary serial data signal
and the clock signal from the CLS200 via the TB50. Any
control output can be configured to provide the data signal.
The Serial DAC also requires a 5V
Î
(dc) power input.
Table 11.36 Serial DAC Inputs
Table 11.37 Serial DAC Power Requirements
CE Directive
Electromagnetic Compatibility (EMC)
directive 89/336/EEC
UL and C-UL
UL 916 Standard for Energy Manage-
ment Equipment File E177240
Parameter
Description
Data
4 mA maximum to DC COM
Open collector or HC CMOS logic levels
Clock
0.5 mA maximum to DC COM
Open collector or HC CMOS logic levels
Parameter
Description
Voltage
4.75 to 5.25V
Î
(dc) @ 300 mA maximum
Current
210 mA typical @ 20V
Î
(dc) out