Cls216 voltage inputs – Watlow CLS200 User Manual
Page 201

CLS200 Series User’s Guide
Chapter 9:Troubleshooting and Reconfiguring
Doc.# 0600-3050-2000
Watlow Anafaze
185
Table 9.13 Resistor Locations for CLS216
Current Inputs
CLS216 Voltage Inputs
For each voltage input on a CLS216 controller, you must in-
stall two resistors. The resistance must be correct for the
expected input range. Install the resistors in the listed lo-
cations.
Table 9.14 Resistor Values for CLS216
Voltage Inputs
Resistor tolerance:
±
0.1%
Loop
Resistor
Location
RD
Loop
Resistor
Location
RD
1
R42
9
R41
2
R40
10
R39
3
R38
11
R37
4
R36
12
R35
5
R34
13
R33
6
R32
14
R31
7
R30
15
R29
8
R28
16
R27
Resistor Values
Input Range
RC
RD
0 to 100mV
Î
(dc)
499
Ω
750
Ω
0 to 500mV
Î
(dc)
5.49 k
Ω
750
Ω
0 to 1V
Î
(dc)
6.91 k
Ω
442.0
Ω
0 to 5V
Î
(dc)
39.2 k
Ω
475.0
Ω
0 to 10V
Î
(dc)
49.9 k
Ω
301.0
Ω
0 to 12V
Î
(dc)
84.5 k
Ω
422.0
Ω