Overshoot reduction, Control type, Table 5.14— control types 115 – Watlow CPC400 User Manual
Page 129

CPC400 Series User’s Guide
Chapter 5: Menu and Parameter Reference
Doc. 0600-2900-2000
Watlow Anafaze
115
Figure 5.3
The Effect of Tune Gain on
Recovery from a Load Change
Overshoot Reduction
Enter the amount of overshoot reduction. A larger value
yields less overshoot.
Values: 0% (0) to 100% (100)
Default: 50% (50)
Modbus Address (Loops 1 to 9): 46576 to 46584
Parameter Number: 146
LogicPro Driver: Database
LogicPro Address (Loops 1 to 9): 146.1 to 146.9
Control Type
Choose a control algorithm.
Table 5.14
Control Types
Values: PID1 (0) or PID2 (1)
Default: PID1 (0)
Modbus Address (Loops 1 to 9): 45480 to 45489
Parameter Number: 139
LogicPro Driver: Database
LogicPro Address (Loops 1 to 9): 139.1 to 139.9
Control Type
Description
PID1
Heat and cool outputs used to control.
Only one output may be on at a time.
PID2
Heat and cool outputs used to control.
Both outputs can be on at the same time.
l01 Overshoot r
reduction b 50%
l01 Control r
type bPID1