Chapter 3: Operation and Setup

CPC400 Series User’s Guide

72

Watlow Anafaze

Doc. 0600-2900-2000

Figure 3.11 Example Application Using Cas-

cade Control

Table 3.10

Parameter Settings for the Primary
Loop in the Cascade Example

Table 3.11

Parameter Settings for the Second-
ary Loop in the Cascade Example

Menu

Parameter

Value

Comment

(none)

Set point

150˚F

Desired temperature at the inner thermocouple.

Control

Ht prop band

10

As the input drops 10°F, the output increases to
100 percent.

Control

Ht integral

0

Only proportional control is used.

Control

Ht derivative

0

Only proportional control is used.

Menu

Parameter

Value

Comment

Cascade

Cascade prim loop

1

Loop 1 is the primary loop.

Cascade

Cascade low SP

150˚F

When the primary loop’s output is 0 percent,
the secondary loop’s set point is 150°F.

Cascade

Cascade high SP

190˚F

When the primary loop output is 100 percent,
the secondary channel set point is 190°F.

CPC400

Water

Power

Controller

Loop 2 PID Output

Heater

Loop 1 Input

Process Variable

Loop 1: Primary Cascade Loop
Loop 2: Secondary Cascade Loop

Loop 2 Input

Process Variable

Outer

Thermocouple

Inner Thermocouple