CPC400 Series User’s Guide
Chapter 6: Troubleshooting and Reconfiguring
Doc. 0600-2900-2000
Watlow Anafaze
159
Current Inputs
For each current input, you must install a resistor. The val-
ue of the resistor must be correct for the expected input
range. Install the resistor in the listed resistor pack (RP) lo-
cation. Note the resistor pack locations have three through-
holes. Install the resistor as shown in the illustration be-
low.
Table 6.3
Resistor Values for Current Inputs
Resistor tolerance:
±
0.1%
Table 6.4
Resistor Locations for Current
Inputs
Input Range
Resistor Value RD
0 to 10 mA
6.0
Ω
0 to 20 mA
3.0
Ω
Loop
Resistor
Location RD
Loop
Resistor
Location RD
1
RP1
5
RP5
2
RP2
6
RP6
3
RP3
7
RP7
4
RP4
8
RP8
RP#
RD