Chapter 6: Troubleshooting and Reconfiguring

CPC400 Series User’s Guide

144

Watlow Anafaze

Doc. 0600-2900-2000

Control mode of one
or more loops
changes from auto-
matic to manual

Failed sensor

Check the display or HMI software for a
failed sensor message.

BCD job selection feature
loaded a different job

Check whether the new job was supposed
to be loaded. If not, check the BCD job
load setup:

Check the settings of the BCD job load
parameters in the

Global setup menu.

Use the

Digital inputs parameter in the I/O

tests menu to test the BCD job load
input(s).

Check the device that is used to activate
job selection.

All loops are in man-
ual mode at 0 per-
cent power

Intermittent power

Check wiring and service. See

Wiring the

Power Supply on page 24.

Use a separate dc supply for the controller.

Provide backup power (uninterruptible
power system).

In the

Global menu, set the Power up loop

mode parameter to from memory if safe for
your application. See

Power Up Loop

Mode on page 100.

Analog reference voltage
overloaded

Disconnect any wiring from the +5V Ref
connection on TB1.

Hardware failure

Check the controller display for a hardware
alarm. See

System Alarms on page 143.

Logic does not run

No logic program loaded

Load a logic program. For more informa-
tion, see the

LogicPro User’s Guide.

Controller not set to run logic
on powerup

Run the logic program; see

Logic Program

on page 99. If desired, set the controller to
start the logic program automatically upon
powerup; see

Power Up With Logic on

page 100.

Controller does not
behave as expected

Corrupt or incorrect values in
RAM

Clear the RAM. See

Clearing the RAM on

page 153.

Symptom

Possible Causes

Recommended Action