Table 7.15—rtd range and resolution 173 – Watlow CPC400 User Manual

Page 187

Advertising
background image

CPC400 Series User’s Guide

Chapter 7: Specifications

Doc. 0600-2900-2000

Watlow Anafaze

173

Table 7.13

Programmable Logic

Table 7.14

Thermocouple Range and
Resolution

* True for 10 percent to 100 percent of span except type B, which is specified
for 800°F to 3200°F.

Table 7.15

RTD Range and Resolution

Programming Languages

Ladder diagram, sequential function chart, function block dia-
gram (IEC 1131-3)

Number of Instructions

7 logic instructions, 42 function block instructions

Memory

64K flash, nonvolatile

Program Execution

Logic program runs concurrently with closed-loop control

Read/Write Access

Controller I/O and closed-loop control parameters

Logic Programming Software

LogicPro

Programming Environment

Windows 95, Windows 98, Windows NT, Windows 2000

Thermocouple

Type

Range in ˚F

Range in ˚C

Accuracy* at

25°C Ambient

Accuracy* at

0 to 50°C Ambient

˚F

˚C

˚F

˚C

J

-350 to 1400

-212 to 760

±2.2

±1.2

±3.3

±1.8

K

-450 to 2500

-268 to 1371

±2.4

±1.3

±3.8

±2.1

T

-450 to 750

-268 to 399

±2.9

±1.6

±5.8

±3.2

S

0 to 3200

-18 to 1760

±5.0

±2.8

±8.8

±4.9

R

0 to 3210

-18 to 1766

±5.0

±2.8

±8.8

±4.9

B

150 to 3200

66 to 1760

±7.2

±4.0

±22.1

±12.3

E

-328 to 1448

-200 to 787

±1.8

±1.0

±2.9

±1.6

Range

in ˚F

Range

in ˚C

Resolution

in ˚C

Measurement

Temperature in

˚C

Accuracy at

25˚C Ambient

Accuracy at

0 to 50˚C Ambient

˚F

˚C

˚F

˚C

-328.0

to

1150.0

-200.0

to

621.1

0.07

25

0.9

0.5

1.2

0.5

400

2.7

1.5

4.1

2.2