CPC400 Series User’s Guide

Chapter 7: Specifications

Doc. 0600-2900-2000

Watlow Anafaze

175

The digital outputs may be used in conjunction with Dual
DAC or Serial DAC modules to provide analog signals. See
Dual DAC Specifications on page 178 and Serial DAC Spec-
ifications on page 180.

Digital Outputs

Table 7.18

Digital Outputs Control / Alarm

Table 7.19

CPU Watchdog Output

Table 7.20

5V

Î

(dc) Output (Power to Operate

Solid-State Relays)

Number

35

Operation

Open collector output; ON state sinks to logic common

Function

34 Outputs selectable as closed-loop control, alarms or pro-
grammable logic. 1 global alarm output

Number of Control Outputs per
PID Loop

2 (maximum)

Control Output Types

Time proportioning, distributed zero crossing, Serial DAC or
on/off. All independently selectable for each output. Heat and
cool control outputs can be individually disabled for use as
alarm outputs

Time Proportioning Cycle Time

1 to 255 seconds, programmable for each output

Control Action

Reverse (heat) or direct (cool), independently selectable for
each output

Off State Leakage Current

<0.01 mA to dc common

Maximum Current

60 mA for each output. 5V power supply (from the processor
module) can supply up to 350 mA total to all outputs

Maximum Voltage Switched

24V

Î

(dc)

Number

1

Operation

Open collector output; ON state sinks to logic common

Function

Monitors the processor module microprocessor

Maximum Current

10 mA (5V power supply in the processor module can supply
up to 350 mA total to all outputs)

Maximum Voltage Switched

5V

Î

(dc)

Voltage

5V

Î

(dc)

Maximum Current

350 mA