Functions Activated by Digital Inputs

Use digital inputs to activate the following functions:

•

Load a job that is stored in controller memory. See
BCD Job Load on page 97.

•

Change all loops to manual mode at specified output
levels. See Mode Override on page 99.

•

Enable thermocouple short detection. See Thermocou-
ple Short Alarm on page 101
.

•

Restore automatic control after a failed sensor has been
repaired. See Restore Automatic Mode on page 114.

TB18 Connections

Table 2.5

TB18 Connections

1

The indicated outputs are dedicated for control when enabled in the

loop setup. If one or both of the outputs are disabled for a loop, then the
corresponding digital outputs become available for alarms or program-
mable logic.

2

If you install a Watlow Anafaze Serial DAC, the CPC400 series control-

ler uses digital output 34 for a clock line. You cannot use output 34 for
anything else if a Serial DAC is installed.

Control Output

1

Terminal

Function

CPC404

CPC408

1

+5V

Î

(dc)

2

CTRL COM

3

Watchdog timer

4

Global alarm

5

Output 1

Loop 1 heat

Loop 1 heat

6

Output 2

Loop 2 heat

Loop 2 heat

7

Output 3

Loop 3 heat

Loop 3 heat

8

Output 4

Loop 4 heat

Loop 4 heat

9

Output 5

Pulse loop heat

Loop 5 heat

10

Output 6

Loop 1 cool

Loop 6 heat

11

Output 7

Loop 2 cool

Loop 7 heat

12

Output 8

Loop 3 cool

Loop 8 heat

13

Output 9

Loop 4 cool

Pulse loop heat

14

Output 10

Pulse loop cool

Loop 1 cool

15

Output 34

2

Serial DAC clock

Serial DAC clock

16

Input 1

17

Input 2

18

Input 3/Pulse input