Voltage Inputs
For each voltage input, you must install two resistors. The
resistances must be correct for the expected input range.
Note the resistor pack (RP) locations have three through-
holes. Install the RD resistor as indicated in the illustra-
tion below.
Table 6.5
Resistor Values for Voltage Inputs
Resistor tolerance:
±
0.1%
Table 6.6
Resistor Locations for Voltage
Inputs
Input Range
Resistor Values
RC
RD
0 to 100mV
Î
(dc)
499
Ω
750
Ω
0 to 500mV
Î
(dc)
5.49 k
Ω
750
Ω
0 to 1V
Î
(dc)
6.91 k
Ω
442.0
Ω
0 to 5V
Î
(dc)
39.2 k
Ω
475
Ω
0 to 10V
Î
(dc)
49.9 k
Ω
301.0
Ω
0 to 12V
Î
(dc)
84.5 k
Ω
422.0
Ω
Loop
Resistor Locations
RC
RD
1
R58
RP1
2
R56
RP2
3
R54
RP3
4
R52
RP4
5
R50
RP5
6
R48
RP6
7
R46
RP7
8
R44
RP8
RP#