33

Table 2.3

Digital Output States and Values
Stored in the Controller

1

Read and write these values through serial communications and Log-

icPro programs.

All digital outputs sink current to controller common when
on. The load may powered by the 5V

Î

(dc) supplied by the

controller at the TB50, or by an external power supply.
When using an external power supply, bear in mind:

The CPC400 power supply available from Watlow
Anafaze includes a 5V

Î

(dc) supply. When using it to

supply output loads, connect the 5V

Î

(dc) common to

the 15V

Î

(dc) common at the power supply.

Do not exceed +24 volts.

If you connect the external load to earth ground, or if
you cannot connect it as shown in Figure 2.21, then
use a solid-state relay.

The outputs conduct current when they are on. The maxi-
mum current sink capability is 60 mA at 24V

Î

(

dc). The

outputs cannot “source” current to a load.

Figure 2.21 Digital Output Wiring

State

Value

1

Description

Off

0

Open circuit

On

1

Sinking current to controller common

Digital Output 1

Digital Output 2

Control Common

+5V

Î

dc

Loads

Digital Output 1

Digital Output 2

Using External Power Supply

Do not connect

External
Power

+

-

TB50 or TB18

Using Internal Power Supply

Loads

Supply

TB50 or TB18

to earth ground or

equipment ground