Chapter 2: Installation

CPC400 Series User’s Guide

44

Watlow Anafaze

Doc. 0600-2900-2000

Cable Recommendations

Watlow Anafaze recommends Belden 9843 cable or its

equivalent. This cable includes three 24 AWG (0.2 mm

2

),

shielded twisted pairs. It should carry signals of up to
19200 baud with acceptable losses for up to 4000 feet (1220
m).

EIA/TIA-485 Network Connections

Watlow Anafaze recommends that you use a single daisy
chain configuration rather than spurs. Run a twisted-pair
cable from the host or converter to the first CPC400, and
from that point run a second cable to the next CPC400, and
so on. See Figure 2.33.

If necessary for servicing, instead of connecting each con-
troller directly to the next, install a terminal strip or con-
nector as close as possible to each CPC400, run a
communications cable from one terminal strip to the next
and connect the controllers to the bus with short lengths of
cable.

To avoid unacceptable interference, use less than 10 feet
(3 m) of cable from the terminal or connector to the CPC400
serial port.

Refer to Termination on page 45 for more on terminating
resistors.

Connect the shield drain to earth ground only at the com-
puter or host end.

Figure 2.33 Recommended System

Connections

Serial Port

232 Communications

485 Communications

Shielded Twisted Pair Cable

First CPC400

Second CPC400

Last CPC400

232-to-485

Converter