Chapter 3: Operation and Setup

CPC400 Series User’s Guide

70

Watlow Anafaze

Doc. 0600-2900-2000

If the primary loop has both heat and cool outputs,
then the set point of the secondary loop is equal to the
Cascade low SP parameter when the cool output is at
100 percent, and is equal to the Cascade high SP when
the heat output is at 100 percent. See Figure 3.9.

If the primary loop has only a heat output, then the set
point of the secondary loop is equal to the Cascade low
SP
parameter when the heat output is at 0 percent,
and is equal to the Cascade high SP parameter when
the heat output is at 100 percent. See Figure 3.10.

If the primary loop has only a cool output, then the set
point of the secondary loop is equal to the Cascade low
SP
parameter when the cool output is at 100 percent,
and is equal to the Cascade high SP parameter when
the cool output is at 0 percent.

Figure 3.9

Secondary Set Point When Primary
Loop Has Heat and Cool Outputs

Figure 3.10 Secondary Set Point When Primary

Loop Has Heat Output Only

Set P

oint of Secondar

y Loop

(Engineer

ing Units)

High Set Point

Low Set Point

-100%

Output of Primary Loop (Percent of Full Scale)

100%

Set P

oint of the Secondar

y Loop

(Engineer

ing Units)

High Set Point

Low Set Point

0%

Output of Primary Loop (Percent of Full Scale)

100%