<3. Parameter Setting>

3-12

IM 01C25T01-06EN

3.2 Basic Setup

IMPORTANT

After setting and sending data with the HART

configuration tool, wait 30 seconds before

turning off the transmitter. If it is turned off

too soon, the settings will not be stored in the

transmitter.

3.2.1 Tag and Device Information

If there are specified when ordering, the desired Tag

No. and device information are set and shipped.

Tag No. and device information can be checked as

follows.

• Procedure to call up the display using by DD

and DTM (excluding EJX HART 5 DTM based

on FDT1.2)

Item

Procedure

Tag

[Root Menu] → Basic setup → Tag

Long tag

(HART 7 only)

[Root Menu] → Basic setup → Long

Tag

Descriptor

[Root Menu] → Basic setup → Device

information → Descriptor

Message

[Root Menu] → Basic setup → Device

information → Message

Date

[Root Menu] → Basic setup → Device

information → Date

• Procedure to call up the display by EJX HART 5

DTM based on FDT1.2

Item

Procedure

Tag

Easy Setup → Tag

or Configuration → HART → Tag

Descriptor

Configuration → Device information 1

→ Descriptor

Message

Configuration → Device information 1

→ Message

Date

Configuration → Device information 1

→ Date

When the Tag No. and device information are

changed, input them based on the following

limitations.

Item

Limitations

Tag

Up to 8 characters or numbers*

1

Long tag

(HART 7 only)

Up to 32 characters or numbers*

2

Descriptor

Up to 16 characters or numbers*

1

Message

Up to 32 characters or numbers*

1

Date

mm/dd/yyyy

- mm: month (2 digits)

- dd: days (2 digits)

- yyyy: years (4 digits)

*1: The characters bounded by the thick line in the following

table can be used.

*2: All characters in the following table can be used.

SP

!

"

#

$

%

&

'

(

)

*

+

,

-

.

/

0

1

2

3

4

5

6

7

8

9

:

;

<

=

>

?

@

A

B

C

D

E

F

G

H

I

J

K

L

M

N

O

P

Q

R

S

T

U

V

W

X

Y

Z

[

\

]

^

_

`

a

b

c

d

e

f

g

h

i

j

k

l

m

n

o

p

q

r

s

t

u

v

w

x

y

z

{

|

}

~

*: SP shows one-byte space

3.2.2 Unit

The unit parameter is set at the factory before

shipment if specified at the time of order. Follow the

procedure below to change the unit parameter.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Basic setup →

Unit

EJX_HART 5[1.2]

DTM

Easy Setup → Unit or

Configuration → Analog Output

→ Unit

Note that the Yokogawa default setting for the

standard temperature is 4°C (39.2°F). For the units

of mmH

2

O, inH

2

O, and ftH

2

O, the pressure varies

according to the standard temperature definition.

Select the appropriate unit with @68degF when a

standard temperature of 20°C (68°F) is required.
Available pressure units are shown below.

inH

2

O@68degF

inHg

ftH

2

O@68degF

mmH

2

O@68degF

mmHg

psi

bar

mbar

g/cm

2

kg/cm

2

Pa

kPa

torr

atm

MPa

inH

2

O

mmH

2

O

ftH

2

O

hPa