5 unit for displayed temperature, 6 sensor trim, Unit for displayed temperature -18 – Yokogawa EJA440E User Manual

Page 31: Sensor trim -18

Advertising
background image

<3. Parameter Setting>

3-18

IM 01C25T01-06EN

Setting by EJX HART 5 DTM based on

FDT1.2

User can input the desired unit at

Engr Unit.

• Procedure to call up the display

EJX HART 5 DTM

based on FDT1.2

Configuration →Local Display →

→ Engr Unit

Set the engineering unit

→ Engr LRV

Lower range value

→ Engr URV

Upper range value

→ Engr exp

Exponents for user scale display

→ Engr point

Decimal point position for user

scale display

Available characters and symbols for

Engr Unit are

the same as for

Modify Engr Unit shown above.

3.3.5 Unit for Displayed Temperature

When the instrument is shipped, the temperature

units are set to “deg C” (Centigrade). Follow the

procedure below to change this setting.
When this parameter is set, it also changes the

temperature unit for

Snsr temp at Process

variables and Amp temp at Temp sensor.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Detailed setup →

Sensors → Temp sensor →

EJX_HART 5[1.2]

DTM

Configuration → Process Input →

→ Temp Unit

Select the temperature unit

(deg C, deg F, Kelvin(K))

3.3.6 Sensor Trim

The transmitter is factory characterized. Factory

characterization is the process of comparing a

known pressure input with the output of each

transmitter sensor module over the entire pressure

and temperature operating range. During the

characterization process, this comparison

information is stored in the transmitter EEPROM. In

operation, the transmitter uses this factory-stored

curve to produce a process variable output (PV), in

engineering units, dependent on the pressure input.
The sensor trim procedure allows you to adjust

for local conditions, changing how the transmitter

calculates process variables. There are two ways

to trim the sensor: a zero trim and a full sensor trim.

A zero trim is a one-point adjustment typically used

to compensate for mounting position effects or

zero shifts caused by static pressure. A full sensor

trim is a two-point process, in which two accurate

end-point pressures are applied (equal to or greater

than the range values), and all output is linearized

between them.

(1) Zero Trim
a. Zeroing—Pres Zero trim
Pres Zero trim
carries out the zero adjustment and

automatically sets the applied “0” input values to the

output value of “0”, keeping the span constant. Use

this setting when the LRV is known to be 0 mmH

2

O.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Diag/Service

→ Calibration → Pres Sensor

trim →

EJX_HART 5[1.2]

DTM

Calibration →

→ Pres Zero trim

Adjust the lower point

b. Level Adjustment—Auto, lower Pt
This zero adjustment calibrates the transmitter

output corresponding to the actual tank level. To

perform this adjustment, first use a glass gauge

or the like to determine the actual tank level, then

enter the correct data as shown below.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Diag/Service →

Calibration → Pres Sensor trim

→ Pres trim →

EJX_HART 5[1.2]

DTM

Calibration → Pres trim →

→ Auto, Lower Pt

Auto trim for 0% point

F0306.ai

25.00 kPa

0.00 kPa

Actual level

13.50 kPa

DPharp span: 0 to 25.00 kPa

Actual level: 13.50 kPa

Transmitter output: 13.83 kPa

DPharp

c. Using External Zero-adjustment Screw

This method permits zero adjustment without

the HART configuration tool. Use a slotted

screwdriver to turn the zero-adjustment screw.

See the hardware manual for details.
Note that the parameter of

Ext SW must be

“Enabled” to perform this adjustment. See

section 3.3.8 for the setting procedure.

Advertising
This manual is related to the following products: