Yokogawa EJA440E User Manual

Page 87

Advertising
background image

<5. Parameter Summary>

5-9

IM 01C25T01-06EN

Function

Label

Item

Contents

Default value Handling

*

1

SP setup

A/G Select

Gauge/Abs select for static

pressure

Gauge or Absolute

Absolute

WD

Atm. Pres Value

Conversion coefficient

101.3 kPa

WD

SP Apply values

Rerange for static pressure

“0%, 100%, or Exit”

MD

SP Damp

Damping time constant for SP

0.00 to 100.00

2.00 s

WD

SP H/L Select

H/L select for static pressure

High or Low

High

WD

SP Min Span

Minimum span for static pressure

RD

SP LRV

Lower range value for static

pressure

Within measurement range

0.0 MPa

WD

SP LSL

Lower sensor limit for static

pressure

RD

SP URV

*3

Upper range value for static

pressure

Within measurement range

WD

SP USL

Upper sensor limit for static

pressure

RD

Status

Device Status

Current operating status

R

Status group 1

Device status information for

hardware

Display the hardware error

R

Status group 2

Device status information for

hardware

Display the hardware error

R

Status group 3

Device status information for

process

Display the process error

(Out of specification)

R

Status group 4

Device status information for

process

Display the process error

(Out of setting range)

R

Status group 5

Device status information for

process

Display the process error

(Alarm)

R

Status group 6

Device status information for data

Display the setting error

R

Status group 7

Device status information for data

Display the setting error

R

Status group 8

Device status information for data

Display the diagnostic alarm

R

Status group 9

Device status information for data

Display the diagnostic alarm

R

Status group 10

HART 7

Device status information for data

Display the simulation mode

R

Ext dev status

HART 7

Extended Device Status

R

Time Stamp

Time Stamp

00:00:00

R

Tag

Tag

Tag number

8 alphanumerics

As specified

W

Long tag

HART 7

Long tag

Max 32 alphanumerics

As specified

W

Temperature

compensation

T.Z. Cmp mode

Temperature compensation mode

Off or On

Off

W

Temp Zero

Zero shift compensation

–99.999 to 99.999%/degC

0.000%/degC

W

Temperature

sensor

Amp temp

Amplifier temperature

R

Snsr temp

Capsule temperature

R

Transfer

function

Xfer fnctn

Output mode

Linear or Sq root

As specified or

Linear

W

Units

Unit

Pressure, Differential pressure unit

As specified or

kPa

W

SP Unit

Static pressure unit

MPa

WD

Temp Unit

Temperature unit

deg C, deg F, or Kelvin

deg C

W

Write

protection

menu

Enable wrt 10min

Write protection release

8 alphanumerics

M

New password

User set password for write

protection

8 alphanumerics

M

Write protect

Write protection indicator

Yes or No

No

R

*1:

Handling:

R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,

D=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.

*2:

Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)

*3:

The default value shows MWP (Maximum working pressure) of the capsule.

Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.