<4. Diagnostics>

4-7

IM 01C25T01-06EN

Table 4.3

Default Values of Limit Parameter

#

Parameter

Differential pressure

transmitter

Flange

mounted

differential

pressure

transmitter

Diaphragm

sealed differential

pressure/

pressure

transmitter

Absolute

pressure

transmitter

Gauge

pressure

transmitter

Gauge/

Absol ute

pressure

transmitter

EJX110A

EJX115A

EJX130A

EJX120A

EJX210A

EJX118A

Note 1

EJX438A

EJX310A

EJX430A

EJX440A

EJX510A

EJX530A

EJX610A

EJX630A

[1]

Lim fDPmax

3

3

10000

10000

10000

10000

10000

[2]

Lim fDPmin

0.3

0.3

0.3

0.3

0.3

0.3

0.3

[3]

Lim fSPlmax

5

10000

10000

10000

10000

10000

10000

[4]

Lim fSPlmin

0.5

0

0

0

0

0

0

[5]

Lim fSPhmax

5

10000

10000

10000

10000

10000

10000

[6]

Lim fSPhmin

0.5

0

0

0

0

0

0

[7]

Lim BlkFmax

0.6

10

10

10

10

10

10

[8]

Lim BlkFmin

-0.6

-10

-10

-10

-10

-10

-10

[9] Lim DPAvgmax

Note 2

1

1

1

1

1

1

1

[10] Lim DPAvgmin

Note 2

0.05

0.2

-1

-1

0.05

0.05

0.05

Note 1: The default values are set for level measurement. If EJX118A is applied to flow measurement, enter the same value to Limit

parameter [1] to [10] as those of EJX110A.

Note 2: It indicates the threshold value for “ILBD over range” (refer to 4.2.2.5).

H/L Blocking Detection

EJX differential pressure transmitter enables

to detect both-, a high-, or low-pressure-side

blockage. The blockage degree characterized

by a comparison of high-pressure side and low-

pressure-side fluctuation values,

BlkF, is used to

detect it. The value changes within a range of –1

to +1. As

BlkF approaches +1, the high-pressure-

side blockage progresses. On the other hand, if it

approaches –1, the low-pressure-side blockage

progresses.

1

0

1

0

F0404.ai

BlkF

Blockage detection for

high-pressure side

Threshold

Blockage Progress

BlkF

Blockage detection for

low-pressure side

Threshold

Blockage Progress

-1

-1

Figure 4.3

Relation between Blockage Progress

and BlkF

The each threshold value to detect the high- or low-

pressure-side blockage is set to

Lim BlkFmax or

Lim BlkFmin.

A/B Blocking Detection

“A Blocking” and “B Blocking” indicates the result

estimated from blockage degree based on the

difference of the high- and low-pressure-side

fluctuation values.

Ratio fDP, SQRT (fDP / Ref

fDP) is used to detect A/B blocking. Ref fDP is the

average value of the sum of squares of differential

pressure fluctuations under normal condition.
As the value of

Ratio fDP exceeds the value of

Lim fDPmax, EJX gives basically an alarm of “A

Blocking”. On the other hand, if this value is below

the value of

Lim fDPmin, EJX gives an alarm of “B

Blocking.
As a high- or low-pressure-side blockage

progresses,

fDP increases. Therefore, “A Blocking”

with a differential pressure transmitter indicates

that a single-side impulse line is plugged for a

differential pressure transmitter. As the both-side

blockages progress simultaneously,

fDP decreases.

Therefore, “B Blocking” with a differential pressure

transmitter indicates that both-side impulse lines

are plugged.

NOTE

A single-side impulse line blockage may

generate “B blocking” under the condition where

the fluctuation amplitude is much different

between high- and low-pressure sides.