Yokogawa EJA440E User Manual

Page 84

Advertising
background image

<5. Parameter Summary>

5-6

IM 01C25T01-06EN

Function

Label

Item

Contents

Default value Handling

*

1

Fluct Variables fDP

Average value of the sum of

squares of differential pressure/

pressure fluctuations

RG

fDP Status

Status of fDP

RG

fSPl

Average value of the sum of

squares of low-pressure-sidestatic

pressure fluctuations

RG

fSPl Status

Status of fSPl

RG

fSPh

Average value of the sum of

squares of high-pressure-side

static pressure fluctuations

RG

fSPh Status

Status of fSPh

RG

Loop test

Loop test

Test output setting

Within AO lower and upper

limits

M

Test Auto Release

Time

Auto release time for the test

function. Coverage is Loop test,

DO test and Device Variable

Simulation.

10min, 30min, 60min, 3h,

6h, 12h

10 min

W

Low cut

Low cut

Low cut

0.00 to 20.00%

Refer to

subsection

3.2.6

W

Low cut mode

Low cut mode

Linear or Zero

Linear

W

Master test

Master test

Software reset and self test

M

Message

Message

Message

32 alphanumerics

As specified

W

Number of

requested

preambles

Num req preams

Number of requested preambles

R

Num resp preams

HART 7

Number of response preambles

5

W

Optional

function

Option Password

Optional function activation

password

W

Piping

orientation

H/L Swap

Impulse piping accessing direction Normal or Reverse

Normal

WD

Poll address

Poll addr

Poll address for multidrop use

0 to 15(HART 5), 0 to

63(HART 7)

0

W

Loop current mode

HART 7

Loop current mode in Multi Drop

mode

(Disabled, Enabled)

Disabled

W

Process Alerts Digital Output

EJX

Display of contact output

Off or On

Off

RA

DO Select

EJX

Contact output select

Off, Combination of Pres, SP

and Temp

Off

WA

DO Signal type

EJX

Signal type select

ON WHEN AL. DETECT, OFF

WHEN AL. DETECT

ON WHEN AL.

DETECT

WA

DO Test

EJX

Test output contact

Status High, Status Low, Exit

MA

Pres Alert Mode

Alert Mode for differential pressure Off, Hi Al Detect,Lo Al Detect,

Hi/Lo Al Detect

Off

W

Hi Alert Val

High alert value for differential

pressure

Set the threshold value for

high side alarm

W

Lo Alert Val

Low alert value for differential

pressure

Set the threshold value for

low side alarm

W

SP Alert Mode

Alert Mode for static pressure

Off, Hi Al Detect,Lo Al Detect,

Hi/Lo Al Detect

Off

WD

SP Hi Alert Val

High alert value for static pressure

Set the threshold value for

high side alarm

WD

SP Lo Alert Val

Low alert value for static pressure

Set the threshold value for

low side alarm

WD

Temp Alert Mode

Alert Mode for temperature

Off, Hi Al Detect,Lo Al Detect,

Hi/Lo Al Detect

Off

W

*1:

Handling:

R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,

D=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.

*2:

Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)

*3:

The default value shows MWP (Maximum working pressure) of the capsule.

Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.

Advertising
This manual is related to the following products: