Yokogawa EJA440E User Manual

Page 75

Advertising
background image

<4. Diagnostics>

4-28

IM 01C25T01-06EN

Table 4.10

Relationship between Alarm and Status available for HART 7

Integral

Indicator

HART configuration

tool display

Device Status

Extended

Device Status

Value and Status (Data Quality and Limit Status)

Differential

Pressure

(DP)

Static

Pressure

(SP)

Temperature

(T)

% range

Loop current

AL.01

CAP.ERR

P sensor error *

1

Pressure Sensor

Error *

2

Device

Malfunction

(0x80)

Maintenance

Required

(0x01)

Value: Hold value

Status: Bad and Constant

Value:Hold value

Status:Bad and Low Limited/

High Limited

*3

CT sensor error *

1

Capsule

Temperature

Sensor Error *

2

Value: Hold value

Status: Bad and Constant

Cap EEPROM

error *

1

Capsule

EEPROM Error *

2

Value: Hold value

Status: Bad and Constant

AL.02

AMP.ERR

AT sensor error *

1

Amp Temp

Sensor Error *

2

Value: Hold value

Status: Bad and Constant

Value: Hold value

Status: Bad and Low

Limited/High Limited

*3

Amp EEPROM

error *

1

Amp EEPROM

Error *

2

Value: Hold value

Status: Bad and Constant

CPU board error

*

1

CPU Board Error

*

2

Value: Hold value

Status: Bad and Constant

---

No device ID *

1

No Device ID *

2

---

---

Value: Measured value

Status: Good and Not Limited

AL.10

PRESS

P outside limit *

1

Pressure Outside

Limit *

2

Primary

Variable Out of

Limits (0x01)

Device

Variable Alert

(0x02)

Value:

Measured value

Status:

Poor Accuracy and Not

Limited

Value:

Measured

value

Status:

Good and Not

Limited

Same as Value and Status

of PV

AL.11

ST.PRSS

SP outside limit *

1

Static Pressure

Outside Limit *

2

Non-Primary

Variable Out of

Limits (0x02)

AL.12

CAP.TMP

CT outside limit *

1

Cap Temp

Outside Limit *

2

Non-Primary

Variable Out of

Limits (0x02)

AL.13

AMP.TMP

AT outside limit *

1

Amp Temp

Outside Limit *

2

Value: Measured value

Status: Good and Not Limited

AL.30

PRS.RNG

P over range *

1

Pressure Over

Range *

2

Loop Current

Saturated

(0x04)

Value: Measured value

Status: Good and Not Limited

Value: Hold value

Status: Bad and Low

Limited/High Limited

*4

AL.31

SP. RNG

SP over range *

1

Static Pressure

Over Range *

2

---

Value: Measured value

Status: Good and Not

Limited

*1: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2)

*2: EJX HART 5 DTM based on FDT1.2

*3: Depend on the setting of hardware switch

*4: Depend on the direction of range over (high or low)

Advertising
This manual is related to the following products: