Yokogawa EJA440E User Manual

Page 32

Advertising
background image

<3. Parameter Setting>

3-19

IM 01C25T01-06EN

(2) Full Sensor Trim—Auto Trim and Manual

Trim

Full sensor trim is carried out by performing

Auto,

Lower Pt followed by Auto, Upper Pt.
Also, you can manually perform the trimming

procedure with

Manual, Lower Pt and Manual,

Upper Pt.
The full sensor trim is a two-point adjustment,

and the lower point adjustment should always be

performed before the upper point adjustment in

order to maintain the pitch between the zero and

100% points within the calibration range.
In the manual method, the reference pressure

should also be applied to the transmitter at both

the lower and upper points. Without the reference

pressure,

Manual, Lower Pt and Manual, Upper

Pt may not represent the correct value for each

adjustment point.
a. Auto Sensor Trim

Applying reference pressure of 0% and 100% of the

measurement range to the transmitter, adjust the

lower and upper points automatically.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Diag/Service →

Calibration → Pres sensor trim →

Pres trim →

EJX_HART 5[1.2]

DTM

Calibration → Pres trim →

→ Auto, Lower Pt Auto trim for 0% point
→ Auto, Upper Pt Auto trim for 100% point

b. Manual Sensor Trim

Using the example below, follow the steps to

perform the full sensor trim by manually. The Pres

LTD (Manual, Lower Pt) and Pres UTD (Manual,

Upper Pt) represent the previously adjusted values.

Example: For the range of 1000 to 3000 mmH

2

O

Pres LTD (Manual, Lower Pt) = −4.0 mmH

2

O

Pres UTD (Manual, Upper Pt) = −3.0 mmH

2

O

<1> Call up the

Manual, Lower Pt.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Diag/Service →

Calibration → Pres sensor trim

→ Pres trim →

EJX_HART 5[1.2]

DTM

Calibration → Pres trim →

→ Manual, Lower Pt Manual trim for 0% point
→ Manual, Upper Pt Manual trim for 100% point

<2> Suppose that a standard pressure of 1000

mmH

2

O is applied and the value of the “Pres

for trim” is 994.0. Correct for this output error

of 6 mmH

2

O by adding 6 mmH

2

O to

Pres LTD

(Manual, Lower Pt).

−4.0+6.0=+2.0

<3> Enter the correction value of “2” to the

Pres

LTD (Manual, Lower Pt).

<4> Call up the

Pres UTD (Manual, Upper Pt).

<5> Suppose that a standard pressure of 3000

mmH

2

O is applied and the value of the Pres for

trim is 3015.0. Firstly, obtain the slope error for

the span as follows;

Slope Error =

×(URV−LRV)

=

× (3000−1000) = −10

3000−3015

3000

Applied Pressure Value−Value of Pres for Trim

Applied Pressure Value

Then correct for this slope error of −10 by

adding −10 to

Pres UTD (Manual, Upper Pt).

−3.0+(−10.0)=−13.0

<6> Enter the correction value of “−13” to the

Pres

UTD (Manual, Upper Pt).

(3) Sensor Trim for Static Pressure
For the transmitter, full sensor trim of the static

pressure is performed in the same way as with the

differential pressure.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Diag/Service

→ Calibration → SP sensor

trim → Static Pres trim →

EJX_HART 5[1.2]

DTM

Calibration → Static Pres trim

→ Auto, Lower Pt

Auto trim for 0% point

→ Auto, Upper Pt

Auto trim for 100% point

→ Manual, Lower Pt

Manual trim for 0% point

→ Manual, Upper Pt

Manual trim for 100% point

(4) Reset Trim Adjistment to Factory Setting
The

Clear P snsr trim and Clear SP snsr trim

commands can reset the trim adjustment to the

initial calibrated values that were set. The amount of

the adjustment performed with the external zero-

adjustment screw is returned to the initial setting as

well.

Advertising
This manual is related to the following products: