Yokogawa EJA440E User Manual

Page 43

Advertising
background image

<3. Parameter Setting>

3-30

IM 01C25T01-06EN

a. Burst Command
Select the transmission data at

Burst Command

parameter.

Burst Command

Command parameter

Cmd1: PV

PV (Pressure • Differential

Pressure)

Cmd2: % range/current % range/current (Percent of

range, Loop current)

Cmd3: Dyn vars/current Process vars/current

(Loop current, Pressure •

Differential Pressure • Static

Pressure • Temperature)

Cmd9: Device vars w/

status

Process vars/% range/current

Mapping by user

Cmd48: Read

Additional Device

Status

Self diagnosis information

b. Burst Variable Code/Device Variable Code
This parameter need to be set when

Burst

Command is Cmd9:Device vars w/status (up to

eight items).

• Procedure to call up the display

DD and DTM

[Root Menu] → Detailed setup

→Output condition →HART output

→ Burst condition → Burst Message

1,2 or 3 → Burst Device Variables

→ Burst Variable Code (DD)/Device

Variable Code (DTM) →

Display Item

Contents

PV

Select the pressure

SV

Select the static pressure

TV

Select the capsule temperature

% rnge

Select the % output

Loop current

Select the output current

Not Used

c. Update period and Max Update Period
Set to

Update Period and Max Update Period.

When the period that is earlier than the operation

period of each process value was set, it is set

automatically to become bigger than an operation

period of the transmitter.

For

Update Period, set the value that is smaller

than

Max Update Period.

• Procedure to call up the display

DD and DTM

[Root Menu] → Detailed setup

→Output condition →HART

output → Burst condition → Burst

Message 1,2 or 3 → Set Burst

Period

→ Update Period

/ Max Update

Period

0.5 s
1 s
2 s
4 s
8 s
16 s
32 s
1 min
5 min
10 min
15 min
30 min
45 min
60 min

d. Burst Msg Trigger Mode
Set the

Burst Msg Trigger Mode from the

parameters shown below.

When

Burst Msg Trigger Mode is Window, Rising

or Falling, set the

Burst Trigger Level.

• Procedure to call up the display

DD and DTM

[Root Menu] → Detailed setup →

Output condition →HART output →

Burst condition → Burst Message 1,2

or 3 → Set Burst Trigger →

Display Item

Contents

Continuous

Burst Message is transmitted

continuously.

Window

In “Window” mode, the Trigger Value

must be a positive number and is the

symmetric window around the last

communicated value.

Rising

In “Rising” mode, the Burst Message

must be published when the source

value exceeds the threshold

established by the trigger value.

Falling

In “Falling” mode, the Burst Message

must be published when the source

value fall below the threshold

established by the trigger value.

On-change

In “On-change” mode, the Burst

Message must be published when the

source value on change established

by the trigger value.