<Appendix2. ILBD Check List>

A2-2

IM 01C25T01-06EN

Checklist (2/5)

No.

Items

Parameters

Result

Example

8

Alarm status

• Check the alarm status shown in

Diag Error.

• Check that the alarm status of “ILBD over

range” is not shown in

Diag Error.

Diag Error

A Blocking

Large Fluct L

Large Fluct H

L Side Blocking

H Side Blocking

B Blocking

Invalid Ref F

Invalid Ref SPH

Invalid Ref SPL

Invalid Ref DP

ILBD over range

9

ILBD parameters

• Record the values of parameters for ILBD

operation.

• Check the status of parameters for ILBD

operation.

*: Record the value after checked that the

status of each parameter is “GOOD”.

Diag Period

180

Lim fDPmax

3.000000

Lim fDPmin

0.300000

Lim fSPlmax

5.000000

Lim fSPlmin

0.500000

Lim fSPhmax

5.000000

Lim fSPhmin

0.500000

Lim BlkFmax

0.600000

Lim BlkFmin

-0.600000

Lim DPAvgmax

1.000000

Lim DPAvgmin

0.050000

Diag Supp Count

3

Ref fDP*

7.43245E-09

Ref fSPl*

7.25765E-09

Ref fSPh*

7.18374E-09

Ref DPAvg*

5.36425E+00

fDP*

7.48562E-09

fSPl*

7.23277E-09

fSPh*

7.14085E-09

BlkF*

-0.287259

DPAvg*

0.055957