<3. Parameter Setting>

3-26

IM 01C25T01-06EN

Setting by EJX HART 5 DTM based on

FDT1.2

Call up the test output parameter (Loop test) and

select either manual test or auto test, and set the

current value.

• Procedure to call up the display

EJX HART 5

DTM based on

FDT1.2

Diag and Service → Service

→ Loop test →

Display Item

Contents

Manual Test

Set the current value or % value at

Test output value, then click the

Start button.

Auto Test

Set the interval and rate of change

of current output at

Auto Test

Setting, then click the Start button.

(2) DO Test (only for EJX series)

EJX

This function performs the contact output test.

(option code: /AL)

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Detailed setup

→Output condition → Process

Alerts → DO config → DO Test →

EJX_HART 5[1.2]

DTM

Diag and Service → Service → DO

test →

Display Item

Contents

Off

Contact output: OFF

On

Contact output: ON

Exit

Output test is canceled

(3) Device Variable Simulation Function

(Effective only when setting to HART 7)

HART 7

Using the simulation function, the output signal can

be confirmed by setting any value and status to the

selected device variable.

Call up the parameter and follow the message

shown.

After completing the step 5, the simulation starts.

Integral indicator shows output value and alarm

(AL.91) alternately.

• Procedure of device variable simulation

Step 1 Call up the

parameter

[Root Menu] → Diag/

Service → Test (DTM)/Test

device (DD) → Simulate

2

Selection of

Device Variable

Select one parameter from

the list below

Off

PV

SV

TV

Percent Range

Loop Current

3

Setting of Value

Input the simulate value

4

Setting of Data

quality

Select one parameter from

the list below

Bad

Poor accuracy

Manual / Fixed

Good

5

Setting of Limit

status

Select one parameter from

the list below

Not limited

Low limited

High limited

Constant

NOTE

• All the simulations for pressure, static

pressure, and capsule temperature are

reflected to the output. Accordingly, the loop

current, LCD display, and communication

output are directly corresponded to the

simulate value.

The alarm output is also available according

to the simulate value.

• Damping is applicable for pressure,

static pressure, and capsule temperature

simulation.

(4) Squawk (Effective only when setting to

HART 7)

HART 7

This feature can be used to identify the

communicating transmitter by remotely causing

LCD to display the particular pattern as shown in

the Figure 3.3.

“SQUAWK” continues for approximately 15

seconds, then is released automatically.

Enter the larger number to “Change number of

squawks to make” in order to prolong the duration

of squawk indication.