Functional block diagram – Yokogawa EJA440E User Manual

Page 52

Advertising
background image

<4. Diagnostics>

4-5

IM 01C25T01-06EN

Functional block diagram

The figure below shows the functional block diagram of ILBD.

EJX

Sensor

Process Value

calculation

Blockage degree

Alarm

Masking

Response Code

(Device Status)

Status group 8,9
Display on LCD

Contact Output

Digital Output

Sensor

signals

DO Config

Ratio fDP

Ratio fSPl

Ratio fSPh

BlkF, fDP

fSPl, fSPh

Diag Applicable

*1

Diag Error

Add result of

blockage detection to status

Pres, Pres %

Engr Disp

SP, SP %

Snsr temp

Amp temp
Output 4-20mA

AO

Execution of

ILBD

Result of blockage detection

Blockage alarm

Blockage alarm

Diag Output

Option

Blockage alarm

Result of blockage detection

-------(6)

F0402.ai

-------(7)

-------(1)

-------(4)

-------(2)
-------(3)
-------(5)

Figure 4.2

Functional Block Diagram of ILBD

The following outputs are given for the ILBD results.

Table 4.1

List of Outputs for ILBD

OUTPUT

Parameter name

Parameters based on the fluctuation value and blockage degree.

[ Diag DPComp: Non-Compensation ]

:

[ Diag DPComp: Compensation ]

:

Blockage degree characterized in comparison of high-pressure side and low-pressure

side pressure fluctuation value.
Average value of the sum of squares of differential pressure fluctuations.
Average value of the sum of squares of low-pressure side static pressure fluctuation.
Average value of the sum of squares of high-pressure side static pressure fluctuation.
After the reference value is obtained, the applicable blockage defection and the status of

abnormal fluctuation are displayed on this parameter.
When an impulse line blockage is detected, “More Status Avairable” is generated in

Response Code Device Status.

Response Code

Device Status

When an impulse line blockage is detected, the result of the blockage detection

(alarm status) is indicated.
When an impulse line blockage is detected, the results of the blockage detection

(alarm status) is indicated.
When impulse line blockage is detected, an alarm status is displayed on LCD.
When impulse line blockage is detected, an alarm status is output on 4 to 20mA.
When impulse line blockage is detected, an alarm status is output on Status output.

#

(1)

(3)

(4)

Status group 8, 9

Diag Error

Ratio fDP

Ratio fSPl

Ratio fSPh

BlkF

(2)

=

Ratio fDP

Ref fDP

fDP

×

DPAvg

Ref DPAvg

=

Ratio fDP

Ref fDP

fDP

=

Ratio fSPl

Ref fSPl

fSPl

=

Ratio fSPh

Ref fSPh

fSPh

Remarks

(5)
(6)
(7)

Display on LCD
Analog Output
Digital Output

fDP
fSPI
fSPh

Diag Applicable*

1

F0403.ai

*1:

Available only for DD and DTM (excluding EJX HART 5 DTM based on FDT1.2).

For EJX HART 5 DTM based on FDT1.2, the color of icon on the Diag Error display changes with the status.