Yokogawa EJA440E User Manual

Page 86

Advertising
background image

<5. Parameter Summary>

5-8

IM 01C25T01-06EN

Function

Label

Item

Contents

Default value Handling

*

1

Process

variables

TV (DD)

Snsr temp (DTM)

Temperature value

Capsule temperature

R

TV (Temp) Data

Quality

HART 7

Device variable process data

quality

Device variable process data

quality of TV (Temp)

Good

R

TV (Temp) Limit

Status

HART 7

Device variable limit status

Device variable limit status of

TV (Temp)

Not limited

R

TV Update time

period (DD)

Temp update time

(DTM)

HART 7

TV (Temp) Update time period

1s

R

Range change Apply values

Re range for measured pressure

4 mA, 20 mA, or Exit

M

Min Span

Minimum span for pressure

R

LRV

Lower range value for pressure

As specified

W

LSL

Lower sensor limit for pressure

R

URV

Upper range value for pressure

As specified

W

USL

Upper sensor limit for pressure

R

Self test

Self test

Self-diagnostics

M

Sensor trim

Clear P snsr trim

Reset pressure trim to factory

setting

M

Clear SP snsr trim

Reset SP trim to factory setting

MD

P LTD

Lower pressure trim deviation

R

P LTP

Lower temperature trim point

R

P UTD

Upper pressure trim deviation

R

P UTP

Upper temperature trim point

R

Pres trim

Pressure trim

M

Pres Zero trim

Zeroing

M

SP LTD

Lower SP trim deviation

RD

SP LTP

Lower SP trim point

RD

SP UTD

Upper SP trim deviation

RD

SP UTP

Upper SP trim point

RD

Static Pres trim

Static pressure trim

MD

Trim Date

Trim date

**/**/**

W

Trim Desc

Trim description

16 alphanumerics

W

Trim Loc

Trim location

8 alphanumerics

W

Trim Who

Trim person

8 alphanumerics

W

Set Diag Mode Set Diag Mode

ILBD operation mode

Stop, Calculation, or

Reference

WG

Signal

characterizer

Num of points

Number of coordinates

0 to 9

9

W

Point setting

Coordinates editor

M

S.C.

Signal characterizer permission

Disabled or Enabled

Disabled

W

X End

End point of X

100.00%

R

X Start

Start point of X

0.00%

R

Y End

End point of Y

100.00%

R

Y Start

Start point of Y

0.00%

R

*1:

Handling:

R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,

D=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.

*2:

Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)

*3:

The default value shows MWP (Maximum working pressure) of the capsule.

Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.