Troubleshooting, 3 large flowmeter errors – Yokogawa digitalYEWFLO (DY) User Manual

Page 106

Advertising
background image

TROUBLESHOOTING

IM 1F2B4-01-YIA

Page 101

6.5.3

Large flowmeter errors

Are power supply

voltage and load

resistance correct?

Do parameter settings agree

with process conditions?

END

Does TP2

waveform contain

60Hz noise?

END

Correct power supply

voltage and load

Correct parameter settings

Correct parameter setting

or process conditions

END

No

No

Recheck meter sizing.

Confirm that flow rate

is betwen Qmin and Qmax.

Yes

Yes

END

Are Reynolds number,

temperature and pressure in

operating range.

(note)

Is TP2-COM2 waveform

normal? Figure 6.4.1.

YES

NO

YES

YES

NO

NO

YES

NO

END

END

Perform piping checkout procedure,
section 6.4.3. Correct as required.

Operating

Normal

Check calibration

standards

Eliminate noise by grounding, or

using shielded wire. (For remote

meters only, confirm that Yokogawa's

special signal cable (YF011)

is used and properly terminated.)

Contact Yokogawa Industrial Automation

technical assistance, 800/524-7378.