Appendix A: Parameter Details

IM 1F2B4-01-YIA
Page 110

Hand Held

Terminal

Data Range

Indicator/Interface

Help / Remarks

Parameter No. and

Name

Prmtr

No.

Code No.

E + 1
E + 2
E + 3
E + 4
E + 5
E - 5
E - 4
E - 3
E - 2
E - 1

1
2
3
4
5
6
7
8
9

10

a number greater than 32000 (regardless of decimal
point) select the appropriate multiplier value. This
value will be used in conjunction with that entered into
parameter B52.

Example: a 500,000 flow span could be entered as:
B51 : E + 4 = 10

4

=10,000

B52 : 50
See “How to adjust Zero and Span” for more details.

B52: Flow Span

0.00001 to 32000

52

0.00001 to 32000 Enter the desired span value. If this value is greater

than 32,000 use a multiplier factor in parameter B51.

B53: Damping

2
4
8
16
32
64
0

53

0
1
2
3
4
5
6

Select the damping required.

B60: Self-check

Good
Error
Read only

No access

Diagnostic self-check. If good is displayed no error
exists. See “How To Use Diagnostics” for details.

C: Set 2

Read only

No access

This signifies the beginning of Menu C which is where
the totalizer, pulse rate and special units may be set.

C01: Total Rate

E 0
E + 1
E + 2
E + 3
E + 4
E + 5
E - 5
E - 4
E - 3
E - 2
E - 1
UNSC*1
UNSC*10
UNSC*100

C1

0
1
2
3
4
5
6
7
8
9

10
11
12
13

Select the totalizer x10 multiplier for the integral
totalizer.
E 0 = 1 (10

0

) flow unit per count

E + 1 = 10 (10

1

) flow units per count

E + 2 = 100 (10

2

) flow units per count

E + 3 = 1000 (10

3

) flow units per count

E + 4 = 10000 (10

4

) flow units per count

E + 5 = 100000 (10

5

) flow units per count

E - 5 = 0.00001 (10

-5

) flow units per count

E - 4 = 0.0001 (10

-4

) flow units per count

E - 3 = 0.001 (10

-3

) flow units per count

E - 2 = 0.01 (10

-2

) flow units per count

E - 1 = 0.1 (10

-1

) flow units per count

UNSC *1 = K factor x 1 = 1 count/pulse input
UNSC*10 = K factor x 10 = 10 counts/pulse input
UNSC*100 = K factor x 100 = 100 counts/pulse input

C02: Pulse Rate

E 0
E + 1
E + 2
E + 3
E + 4
E + 5
E - 5
E - 4
E - 3
E - 2

C3

0
1
2
3
4
5
6
7
8
9

Select the pulse output x10 multiplier
E 0 = 1 (10

0

) flow unit per pulse

E + 1 = 10 (10

1

) flow units per pulse

E + 2 = 100 (10

2

) flow units per pulse

E + 3 = 1000 (10

3

) flow units per pulse

E + 4 = 10000 (10

4

) flow units per pulse

E + 5 = 100000 (10

5

) flow units per pulse

E - 5 = 0.00001 (10

-5

) flow units per pulse

E - 4 = 0.0001 (10

-4

) flow units per pulse

E - 3 = 0.001 (10

-3

) flow units per pulse

E - 2 = 0.01 (10

-2

) flow units per pulse