Parameter setting/configuration – Yokogawa digitalYEWFLO (DY) User Manual

Page 91

Advertising
background image

IM 1F2B4-01-YIA
Page 86

PARAMETER SETTING/CONFIGURATION

Figure 5.1.2: Integral Indicator/Totalizer Setting and Display Sections

Once in the “SET” mode change the parameter item number using the INC key and move the
flashing digits using the SHIFT key. Press the se

t key to move to the setting mode. Change the

parameter data value and the decimal point position using the Inc key and shift the flashing digit
using the SHIFT key. Once the parameter has been set correctly, press the se

t key once. The

entire display will then flash. Confirm the setting by pressing the se

t again. The flashing will stop.

The parameter is then set. When all parameter settings have been correctly set, press se

t and

SHIFT keys simultaneously. The display is now returned to the normal mode. If the setting has
been done outside the proper operating parameters, alarm is displayed.

•Setting Mode

The display mode can be changed using either the BT100 using parameter “E02: Disp Select” or the
integral indicator/totalizer (TBL) by using the E2 parameter item.

Caution :

While in the setting mode using the TBL, do not access the amplifier using the BT100, Centum

or XL distributed control system with BRAIN™ communications.

•Alarm Number Display Mode

When an alarm occurs, alarm number display and normal display are alternately displayed on the TBL
to indicate an alarm condition exists, provided the TBL is in the normal mode.