•Max. Entity Parameters
Vmax = 28 Vdc
Imax = 93 mA
Pmax = 0.66W
Analog Output
Pulse Output
Ci
4 nF
62 nF
Li
0 mH
0 mH
•Installation Requirements
Vmax > Voc or Vt
Imax > Isc or It
Ca > Ci + Ccable
La < Li + Lcable
Notes:
1.
YF011 signal cable max length 20 meters.
2.
Maximum non-hazardous location voltage must not exceed 250v.
3.
Do not alter drawing without authorization from FMRC.
4.
Installation should be in accordance with ANSI/ISA RP12.6. "Installation of Intrinsically Safe
Systems for Hazardous (Classified) Locations" and the National Electrical Code (ANSI/NFPA
70).
5.
Approved dust-tight seals are required for Class II and III installations.