<10. CALIBRATION SERVICES>

IM 21B04C50-01E

10.1.1 Find Range Result

Display the result of the calibration execution after GO button is pressed.

10.1.2 GO

Start button to execute the selected calibration.

Figure 10.2 Warning

10.1.3 Auto Stop Limits

When Auto Stop Limits is selected, press GO button to execute the automatic position
calibration process. The actuator will be fully exhausted, then fully filled. The position at
each stop will be measured and saved. In some cases when the actuator size is extremely
large, the process may time out and the Manual Stop Limits can be used instead.

For further information about error messages, see YVP User’s manual (IM 21B04C01-01E).