<5. FOUNDATION FIELDBUS OVERVIEW>

When the positioner is receiving its position setpoint from a remote computer system such
as a DCS then the normal state for the positioner will be as shown in Figure 5.12. In this
example the level control valve LV201 is receiving its signal from a DCS. The AO block is
shown in RCas mode.

Figure 5.12 Remote Cascade Normal State

If an internal PID is used in a cascade where the PID receives a setpoint from a remote
computer system, then the normal state will have the PID in RCas mode and the AO will be
in Cas mode (not shown).