Servo Time (duration)

If the duration in which the I/P module operating point is out of the range from Servo Warn-
ing Low to Servo Warning High reaches this set time, block alarm “Servo output drift warn-
ing” is generated. If the duration in which the I/P module operating point is less than 10% or
more than 90% reaches this set value, block alarm “Severe servo output drift” is generated.
A negative value turns off these I/P module operating point warning detection functions.

Servo Warning Count

Number of times of generation of block alarm “Servo output drift warning.”

To reset servo warning count to zero can be performed from General tab of Diagnostics.

9.2.6

Advanced

Refer to Advanced Position.

9.2.7

Configuration - Advanced Position

This is the page for advanced position control parameters configuration contained in
Transducer (TB) block. It is intended for technician use only. It lists here as read only. To
modify the value of any parameter, go to Calibrate Advanced Position.

Figure 9.3 Advanced Servo Tuning Parameters