<9. CONFIGURATION SERVICES>

9.4

Configuration - AO Block

This is the setup page related to the setpoint that is received from another function block or
a remote application. And I/O option contained in Analog Output (AO) Block.

Figure 9.5 Configuration - AO Block

9.4.1

Limits

Setpoint High Limit (%)

Use this to limit the setpoint from another function block or remote application.

Setpoint Low Limit (%)

Use this to limit the setpoint from another function block or remote application.

Setpoint Rate High Limit (%/s)

The setpoint from another function block or remote application may also be limited to
change at a configurable ramp rate. The ramp rate up and the ramp rate down may be
individually configured. The default value is 1.#INF (infinity) which eliminates ramp rate
limiting.

Setpoint Rate Low Limit (%/s)

See Set Point Up Rate Limit (%/s)

NOTE

The AO Block setpoint limits are different from the Position limits configured in the
Configure Position tab. The Position Limits apply to Target Position.