11.1 States and Modes

The permitted states of the PID block are:

RCas selected by the R button. In this mode, the setpoint of the PID block is set by a
remote application that writes to the RCAS_IN parameter regularly. This mode is
allowed only if a remote application is “soft-wired” to the RCAS_IN parameter of the
PID block.

Cas selected by the C button. In this mode, the setpoint of the PID block is set by a
Foundation fieldbus function block. This mode is allowed only if a Foundation fieldbus
function block OUT is “soft-wired” to the CAS_IN parameter of the PID block, and
scheduled.

Auto selected by the L button. In this mode, the setpoint of the PID block is set by the
setpoint slider or the setpoint text box.

Man selected by the M button. In this mode, the output of the PID is set by the output
slider or the output text box. The PID algorithm is not processed in Man.

Simulate selected by the SIM. Button. The ValveNavi user must have the permission
level 8 (training level).

Note that Simulate should never be used with a device that is connected to a real process.
Simulate will destroy any existing control linkages. See 11.3 before actually using this
function.

Other (usually IMan or OOS) indicated by Other button. This button is an indicator
only. It will not change the mode of the PID block.