10-13

IM 21B04C50-01E

<Toc> <Ind>

<10. CALIBRATION SERVICES>

X Boost Off Threshold 1 and X Boost Off Threshold 2 (Exhaust Boost Off

Threshold 1/2)

This control parameter makes the boost on the exhaust side asymmetric to that on the air
supply side. Based on the Boost Off Threshold 1 and Boost Off Threshold 2 values, input a
difference for change.

X Boost Value 1 and X Boost Value2 (Exhaust Boost Value 1/2)

This control parameter makes the boost on the exhaust side asymmetric to that on the air
supply side. Based on the Boost Value 1 and Boost Value 2 values, input a difference for
change.

0

–10

to

10

%

X Boost On Threshold 1

Initial Value

Range of Values

Units

Parameter

X Boost On Threshold 2

0

–10

to

10

%

X Boost Off Threshold 1

0

–10

to

10

%

X Boost Off Threshold 2

0

%

X Boost Value 1

0

–50

to

50

–10

to

10

% of MV

X Boost Value 2

–50

to

50

% of MV

0

T1003.EPS