Figure 13.7 Download Warning Dialog

IMPORTANT

After the download is complete, the device must remain powered for at least 60 seconds to
transfer the data to permanent memory.

13.4 Copy a Configuration to a New Positioner

To copy a configuration from a positioner to another positioner without file saving, select a
source device in the device selection frame and wait until ValveNavi completes reading the
configuration from the device. Then, select the OFFLINE icon but do not open a .dmp file.
The configuration of the previously selected device remains open in ValveNavi. You may
wish to disconnect the source device from the fieldbus segment to prevent accidentally
altering its configuration. While in OFFLINE state, open Configuration Services and type in
the correct Tag and Node Address. Then, right click on Offline or use the download icon to
open the Download Selection dialog (Figure 13.3).

After configuration it is necessary to create the control function block linkages in a third
party fieldbus configurator.

WARNING

The download of this data will overwrite all device configuration data.