6 finish-setup wizard, Finish-setup wizard -8 – Yokogawa YVP20S User Manual

Page 77

Advertising
background image

8-8

<Toc> <Ind>

<8. SETUP WIZARD>

IM 21B04C50-01E

Servo Warning High

If the operating point of the I/P module is more than this value, the timer that measures the
time after the I/P module operating point error starts.

Servo Warning Low

If the operating point of the I/P module is less than this value, the timer that measures the
time after the I/P module operating point error starts. Input a value that is less than that for
Servo Warning High.

Servo Time (duration)

If the duration in which the I/P module operating point is out of the range from Servo Warn-
ing Low to Servo Warning High reaches this set time, block alarm “Servo output drift warn-
ing” is generated. If the duration in which the I/P module operating point is less than 10% or
more than 90% of the range reaches this set value, block alarm “Severe servo output drift”
is generated. A negative value turns off these I/P module operating point warning detection
functions.

Servo Warning Count

Number of times of generation of block alarm “Servo output drift warning.”

To reset servo warning count to zero can be performed from General tab of Diagnostics.

8.6

Finish-Setup Wizard

This is the final screen of the Setup Wizard that indicates that the basic setup is valid and
that provides a choice of Device Operation State before completing this setup. The Wizard
is not completed until the Finish button is pressed.

Figure 8.10 Setup Wizard Finished