Warning – Yokogawa YVP20S User Manual

Page 19

Advertising
background image

3-5

IM 21B04C50-01E

<Toc> <Ind>

<3. INSTALLATION OF HARDWARE AND SOFTWARE>

Configuring the interface card to safely connect to the Foundation fieldbus

segment with a host computer

If the YVP positioner is connected on a segment that has a host computer, the interface
card and PC must be configured as a BASIC DEVICE at a Visitor address. Open the
configuration utility (NI-FBUS Interface Configuration Utility) and follow the instructions in
the NI manual.

Select Port and click Edit to bring up the Port dialog shown in Figure 3.2. Set the
parameters exactly as shown in the figure, and click OK. (The Device Tag can be set to any
name that will be meaningful when seen by a remote interface operating on the same
segment.)

WARNING

ValveNavi is the tool for setup and maintenance. Do not connect it to the operating process.
That may change the mode of YVP and cause unpredictable stop or events on the process.
Use it only when the process is OFFLINE.

Figure 3.2 NI-FBUS Interface configuration utility setting the card as a Basic Device