<9. CONFIGURATION SERVICES>

9.5.3

PV Scale

Units

The engineering units code used for PID process variable.

Upper Range (EU100)

Upper limit value

Lower Range (EU0)

Lower limit value

9.5.4

Configuration - PID Options

This setup page consists of both Control Options and Status Options for PID block. For
each parameter, it is enabled/disabled if it is checked/unchecked.

Figure 9.7 PID Control and Status Options

PID Control and Status Options

Bypass Enable

The normal control algorithm may be bypassed through the BYPASS parameter. When
bypass is set, the setpoint value (in percent) will be directly transferred to the output. To
prevent a bump on transfer to/from bypass, the setpoint will automatically be initialized to
the output value or process variable, respectively, and the path broken flag will be set for
one execution. BYPASS is not permitted unless the BYPASS ENABLED option is set.

SP-PV Track in Man

Permits the setpoint to track the process variable when the target mode of the block is Man.

SP-PV Track in ROut

Permits the setpoint to track the process variable when the actual mode of the block is
ROut.