Internal gain, Servo offset – Yokogawa YVP20S User Manual

Page 110

Advertising
background image

10-12

<Toc> <Ind>

<10. CALIBRATION SERVICES>

IM 21B04C50-01E

Internal Gain

This position control parameter shows the total gain for an I/P module, control relay and
valve.

Servo Offset

Initial valve of an integrator.

Table 10.2 Advanced Servo Tuning Parameters Ranges

1.9

0 (disables);
0.1 to 10.

%

Boost On Threshold 1

2.9

0 (disables);
0.1 to 10. (1)

≥ (2)

%

Boost Off Threshold 1

Boost On Threshold 2

1

0 (disables);
0.1 to 10.

%

Boost Off Threshold 2

1

0 (disables);
0.1 to 10.

%

Boost Value 1

8

0 to 50

% of MV

Boost Value 2

10

0 to 50

% of MV

Servo I Sleep Lmt

0 to 10

seconds

Servo P Alpha

0 (Off)

0

0 to 100

%

Internal Gain

5

0.5 to 50

rad. /mA

Servo Offset

50

0 to 100

% of MV

T1002.EPS

Parameter

Initial Value

Range of Values

Units

In the case of the double acting actuator type, clicking on the More button allows for setting
the following parameters for the double acting actuator type.

Figure 10.12 Advanced Servo Parameters (doubleacting)

X Boost On Threshold 1 and X Boost On Threshold 2 (Exhaust Boost On

Threshold 1/2)

This control parameter makes the boost on the exhaust side asymmetric to that on the air
supply side. Based on the Boost On Threshold 1 and Boost On Threshold 2 values, input a
difference for change.